63A Type B RCBO | EV Charging Circuit Breaker
EKL5-63B is a EV charging station using type B RCBO with Intertek, CE, CB certificated, maxmum current is 63A, Ambient temperature is -25℃-+55℃
Product Profile
Product Profile
EKL5-63B B type RCBO is a electronic type RCD with MCB,it can protection B type wave form of the earth leakage sensed and also have DC smooth direct residual currents and loverload and short circuit protection,according to IEC61851 standard, it can working as the EV Charging station RCD, we normally using 3.7kW (1P+N 20A B curve 30mA), 7.3KW (1P+N 32A B curve 30mA). 11KW (3P+N 20A B curve 30mA), 22KW (4P+N 32A B curve 30mA)
Technical Data
Technical Data
Electrical Features
| Mode | Electronic |
| Type | B |
| Rated current In | 16,20,25,32,40,50,63A |
| Poles | 2P(1P+N), 4P(3P+N) |
| Rated voltage Ue | 2P 240V~ |
| 4P 415V~ | |
| Insulation voltage Ui | 500V |
| Rated frequency | 50/60Hz |
| Rated residual operating current(I△n) | 30mA |
| Break time under I△n | ≤0.1s(S type <0.5s) |
| Rated breaking capacity | 10,000A |
| Energy limiting class | 3 |
| Rated impulse withstand voltage (1.5/50) Uimp | 4,000V |
| Dielectric test voltage at ind.Freq. for 1min | 2kV |
| Pollution degree | 2 |
| Thermo-magnetic release characteristic | B,C |
Mechanical Features
| Electrical life | 4,000 Cycles |
| Mechanical life | 10,000 Cycles |
| Contact position indicator | Yes |
| Protection degree | IP20 |
| Reference temperature for setting of thermal element | 30℃ |
| Ambient temperature (with daily average ≤35°C) | -25℃~+55℃ |
| Storage temperature | -25℃~+70℃ |
Installation
| Terminal connection type | Cable/ Pin-type busbar/ U-type busbar |
| Terminal size top/bottom for cable | 25mm² 18-3AWG |
| Terminal size top/bottom for busbar | 25mm² 18-3AWG |
| Tightening torque | 2.5Nm 22In-lbs |
| Mounting | On DIN rail EN60715(35mm) by means of fast clip device |
| Connection | From top |
Combination With Accessories
| Auxiliary contact | EKM1-OF |
| Alarm contact | EKM1-FB |
| Shunt release | EKM1-MX |
Tripping Current Range
| Lagging Angle | I△n> 0.01A | I△n> 0.01A |
| 0° | 0.35I△n≤I△≤1 4I△n | 0.35I△n≤I△≤2I△n |
| 90° | 0.25I△n≤I△≤1.4I△n | 0.25I△n≤I△≤2I△n |
| 135° | 0.11I△n≤I△≤1 4I△n | 0.11I△n≤I△≤2I△n |
Tripping Current Range
| Detectable wave form | Pulsating direct current sensitive | Surge current proof |
|
B class Tripping is ensured for sinusoidal AC |
They react to AC and pulsating DC |
RCCB'S surge capacity. |
Characteristics Curves

Dimensions
Dimensions
Overall and Installation Dimension(mm)